How do I ensure the CO reading is maximized for CO Air Free on the CAT45 and CAT85?

Fieldpiece Combustion Analyzers (CAT45, CAT85) that have firmware version v1.1 and earlier do not default the CO AIR FREE value to the highest reading, which is also known as [COAF], [CO Undiluted], or [CO at 0% O2 Reference].

To ensure the CO AIR FREE reading is correct, the user should go to Settings and change the O2 Reference from the default number of 6% to 0% [zero oxygen].  This change accurately displays the CO AIR FREE value to comply with BPI-1200 and AHRI 1260 Standards.

Details can be found in this technical bulletin.